Structure design and indirect adaptive general predictive temperature control of a class of passive HVAC.

Abstract : This study focuses firstly on the numerical investigation of an air conditioning unit prototype developed to guarantee a microclimate with controlled temperature and relative humidity set points for crop growth chambers. Numerical techniques based on Computational Fluid Dynamics (CFD) were implemented to estimate component size and to analyze the flow characteristics of the mixed air produced by the device. Simulations disclose a non-linear relationship between the air flow rate and the aperture opening, and also show that the mixing zone was not perfect but could be improved by the addition of baffles. The promising results obtained from CFD were used to improve the automation of the device for potential application in closed greenhouses. Secondly, the indirect adaptive generalized predictive control strategy (IAGPC) with a decentralized architecture was used to control the temperature of the air conditioning unit. As the process involves time-varying, the use of a recursive estimation approach with a fixed forget factor was adopted to estimate in real time the system parameters, and to adapt simultaneously the GPC controller parameters. In order to achieve a local and global efficient performance, the proposed decentralized IAGPC architecture was applied to two principal subsystems, which compose the global unit. A significant real time experimental improvement in the system performance is observed on temperature control for a wide range of operating points.
Type de document :
Article dans une revue
WSEAS Transaction on Systems and Control, 2008, 6 (3), pp.493-502
Liste complète des métadonnées

Littérature citée [30 références]  Voir  Masquer  Télécharger

https://hal-agrocampus-ouest.archives-ouvertes.fr/hal-00729913
Contributeur : Céline Martel <>
Soumis le : jeudi 7 mars 2013 - 14:41:02
Dernière modification le : mercredi 21 mars 2018 - 16:08:05
Document(s) archivé(s) le : lundi 17 juin 2013 - 11:07:23

Fichier

Tawegoum.pdf
Fichiers éditeurs autorisés sur une archive ouverte

Identifiants

  • HAL Id : hal-00729913, version 1

Citation

Rousseau Tawegoum. Structure design and indirect adaptive general predictive temperature control of a class of passive HVAC.. WSEAS Transaction on Systems and Control, 2008, 6 (3), pp.493-502. 〈hal-00729913〉

Partager

Métriques

Consultations de la notice

161

Téléchargements de fichiers

127